PRODUCTS  

High-voltage current limiting fuse for transformer protection(DIN stardand)

Product description: This product applies to the indoor AC 50 ~ 60Hz system with the rated voltage of 3.6~40.5kV, and may be used along with other switching devices (such as load switch, vacuum contactor, etc.) as short-circuit and overload protection element for the power transformer and other power equipment. The product is also essential for the high-voltage switchgear, ring main unit, high/low-voltage pre-installed substation. ModelGB model:XRNT3A-□/□-50Overseas equivalent model: Basic parameters Product Model Equivalent Model Rated Voltage (kV)Rated Current of Fuse Element (A) Standard SizeRated Breaking Current (kA)L(mm)φA(mm)XRNT3A-7.2SDODJ7.23.15, 6.3, 10, 16, 20, 25, 31.5, 40192φ5150SEODJ50, 63, 80φ66SFODJ100, 125φ76SXODJ160, 200φ88SDLDJ6.3, 10, 16, 20, 25, 31.5, 40, 50292φ51SELDJ63, 80, 100φ66SFLDJ125, 160φ76SXLDJ200, 250, 315φ88SEMDJ100, 125442φ66SFMDJ160, 200φ76SXMDJ250, 315, 355φ88XRNT3A-12SDODJ121, 2, 3.15, 6.3, 10, 12192φ5150SELDJ16, 20, 25, 31.5, 40φ66SFODJ50, 63φ76SDLDJ3.15, 6.3, 10, 16, 20, 25, 31.5, 40292φ51SELDJ50, 63, 80φ66SFLDJ100, 125φ76SXLDJ160, 200φ88SDMDJ6.3, 10, 16, 20, 25, 31.5, 40, 50442φ51SEMDJ63, 80, 100φ66SFMDJ125, 160φ76SXMDJ200, 250φ88XRNT3A-24SDLDJ242, 3.15, 6.3, 10, 12292φ5131.5SELDJ16, 20, 25, 31.5, 40φ66SFLDJ50, 63φ76SDMDJ6.3, 10, 16, 20, 25, 31.5, 40442φ5150SEMDJ40, 50, 63φ66SFMDJ63, 80φ76SXMDJ100, 125φ88SFQDJ63, 80, 100537φ76SXQDJ125, 160φ88XRNT3A-40.5SDMDJ40.52, 3.15, 6.3, 10, 12442φ5131.5SDQDJ2, 3.15, 6.3, 10, 16, 20537φ51SEQDJ20, 25φ66SFQDJ31.5, 40φ76SXQDJ50, 56, 63φ88
Model: XRNT
Type: High Voltage Current-Limited Fuse
Applicable: High Voltage
Colour:

5

Origin:
XiangYuan ZhenLi
  • Parameter
  • Specification
  • Service

This product applies to the indoor AC 50 ~ 60Hz system with the rated voltage of 3.6~40.5kV, and may be used along with other switching devices (such as load switch, vacuum contactor, etc.) as short-circuit and overload protection element for the power transformer and other power equipment. The product is also essential for the high-voltage switchgear, ring main unit, high/low-voltage pre-installed substation.

 

Model

GB modelXRNT3A-□/□-50

Overseas equivalent model:

High-voltage current limiting fuse for transformer protection(DIN stardand) 

Basic parameters

Product Model

Equivalent Model

Rated Voltage

(kV)

Rated Current of Fuse Element (A)

 Standard Size

Rated Breaking Current

(kA)

L(mm)

φA(mm)

XRNT3A-7.2

SDODJ

7.2

3.15, 6.3, 10, 16, 20, 25, 31.5, 40

192

φ51

50

SEODJ

50, 63, 80

φ66

SFODJ

100, 125

φ76

SXODJ

160, 200

φ88

SDLDJ

6.3, 10, 16, 20, 25, 31.5, 40, 50

292

φ51

SELDJ

63, 80, 100

φ66

SFLDJ

125, 160

φ76

SXLDJ

200, 250, 315

φ88

SEMDJ

100, 125

442

φ66

SFMDJ

160, 200

φ76

SXMDJ

250, 315, 355

φ88

XRNT3A-12

SDODJ

12

1, 2, 3.15, 6.3, 10, 12

192

φ51

50

SELDJ

16, 20, 25, 31.5, 40

φ66

SFODJ

50, 63

φ76

SDLDJ

3.15, 6.3, 10, 16, 20, 25, 31.5, 40

292

φ51

SELDJ

50, 63, 80

φ66

SFLDJ

100, 125

φ76

SXLDJ

160, 200

φ88

SDMDJ

6.3, 10, 16, 20, 25, 31.5, 40, 50

442

φ51

SEMDJ

63, 80, 100

φ66

SFMDJ

125, 160

φ76

SXMDJ

200, 250

φ88

XRNT3A-24

SDLDJ

24

2, 3.15, 6.3, 10, 12

292

φ51

31.5

SELDJ

16, 20, 25, 31.5, 40

φ66

SFLDJ

50, 63

φ76

SDMDJ

6.3, 10, 16, 20, 25, 31.5, 40

442

φ51

50

SEMDJ

40, 50, 63

φ66

SFMDJ

63, 80

φ76

SXMDJ

100, 125

φ88

SFQDJ

63, 80, 100

537

φ76

SXQDJ

125, 160

φ88

XRNT3A-40.5

SDMDJ

40.5

2, 3.15, 6.3, 10, 12

442

φ51

31.5

SDQDJ

2, 3.15, 6.3, 10, 16, 20

537

φ51

SEQDJ

20, 25

φ66

SFQDJ

31.5, 40

φ76

SXQDJ

50, 56, 63

φ88

 


Main technical data

1. The fuse under specified operating conditions is able to reliably break any fault current from the minimum breaking current to the rated breaking current.

2. This product applies to the indoor AC 50 ~ 60Hz system.

3. Time - current characteristic curve, as shown in Fig. 2, Fig. 3 and Fig. 4, the part above the minimum breaking current is indicated with dotted line.

4. Current limiting characteristic curve is as shown in Fig. 5.

5. I2t characteristic curve is as shown in Fig. 6.

High-voltage current limiting fuse for transformer protection(DIN stardand) 

   Fig. 2 XRNT3A-12 time - current characteristic curve

 

High-voltage current limiting fuse for transformer protection(DIN stardand)

Fig. 3 XRNT3A-24 time - current characteristic curve          

High-voltage current limiting fuse for transformer protection(DIN stardand) 

Fig. 4 XRNT3A-40.5 time - current characteristic curve         

 

High-voltage current limiting fuse for transformer protection(DIN stardand) 

Fig. 5 XRNT3A current limiting characteristic curve

 

High-voltage current limiting fuse for transformer protection(DIN stardand)

                           Fig. 6 XRNT3A I2t characteristic curve

 

Selection of fuse

General selection principle for primary fuse of transformer

 

Rated Voltage  (kV)

Rated Capacity of Transformer (kVA)



100

125

160

200

250

315

400

500

630

800

1000

1250

1600

2000

Rated Current of High-voltage Fuse (A)

6/7.2

16

20

20

25

31.5

40

50

63

80

100

125

160

200

250

10/12

10

16

16

20

25

31.5

40

50

63

80

80

100

125

160

15/17.5

6.3

10

10

16

16

20

25

31.5

40

50

80

80

100

125

20/24

6.3

10

10

10

16

16

20

25

31.5

40

50

63

80

100

35/40.5

3.15

6.3

6.3

6.3

10

10

16

16

20

25

31.5

40

50

56

 

 

Outline drawing of non-standard fuse link

High-voltage current limiting fuse for transformer protection(DIN stardand) 

 

Fig. 7 XRNT3A-40.5/6.3A50A

 

 

 

High-voltage current limiting fuse for transformer protection(DIN stardand) 

Fig. 8 XRNT3A-40.5/6.3A50A

               




XRNT

Hot Products / Hot Products More
2018 - 08 - 30
Type:EV17-□-□VDC/□APerformance coincidence:IEC60269;GB/T31465 ;JASO D622Rated voltage: AC 250V,690V;DC 150V,500V,750VRated current:10A-500ABreaking capacity:AC:100KA; DC:20KAProtective Type:aRInstallation mode:Bolted connectionCharacteristic:Small size, low power consumption, high breaking ability, time constant T Suitable for:Short circuit protection for large, medium and small passenger cars, pa...
Copyright © 2005 - 2013 ShaanXi ZhenLi Electric Power Technology Co.,Ltd.
犀牛云提供企业云服务    
   
Sweep the concern our letter
Address:No.2055,Shanglinyuan 5th Road, High-tech district, Xi'an City Shaanxi Province, China 
Tel: 86 029-86795471
Fax: 86 029-86307131
Zip Code:330520
Share to:
X
等待加载动态数据...

等待加载动态数据...

3

SKYPE 设置

4

阿里旺旺设置

5

TEL:

6

二维码管理

展开