Outline dimensions
Fig. 1 Outline dimensions of XRNT3A full range fuse
Main technical data
Fig. 2 FFL, FXL 12kV time - current characteristic curve
Fig. 3 FDM, FFM 24 time - current characteristic curve
Fig. 4 F fuse current limiting characteristic curve
Selection of fuse
General selection principle for primary full range fuse of transformer
Rated Voltage (kV) | Rated Capacity of Transformer (kVA) |
125 | 160 | 200~250 | 315 | 400 | 500 | 630 | 800 | 1000 |
Rated Current of Full Range High-voltage Fuse (A) |
12 | 10 | 16 | 20 | 25 | 31.5 | 40 | 50 | 63 | 80 |
24 | 6.3 | 10 | 16 | 20 | 25 | 31.5 | 40 |
|
|